Siemens SIMEAS P Power Meter


SIMEAS P is a power meter for panel mounting with graphic display and background illumination. The major application area is power monitoring and recording at MV and LV level. The major information types are measured values, alarms and status information. Power monitoring systems with SIMEAS P, a permanently installed system, enables continuous logging of energy-related data and provides information on operational characteristics of electrical systems. SIMEAS P helps identify sources of energy consumption and time of peak consumption. This knowledge allows you to allocate and reduce energy costs.
Measured values include r.m.s values of voltages (phase-to-phase and/or phase-to-ground), currents, active, reactive and apparent power and energy, power factor, phase angle, harmonics of currents and voltages, total harmonic distortion per phase plus frequency and symmetry factor.

This digital power meter for panel mounting can be used in Measurement Circuit for 3-phase AC Power.


Picture 1: Siemens SIMEAS P Power Meter


The SIMEAS P comes with two binary outputs, which can be configured for energy pulses, limit violations or status signals. The unit is also able to trigger on settable limits. This function can be programmed for sampled or r.m.s. values. SIMEAS P generates a list of minimum, average and maximum values for currents, voltages, power, energy, etc. lndependent settings for currents, voltages, active and reactive power, power factor, etc. are also possible. In case of a violation of these limits, the unit generates alarms. Up to 6 alarm groups can be defined using AND/OR for logical combinations. The alarms can be used to increase counter values, to trigger the oscilloscope function, to generate binary output pulses, etc. The inputs and outputs of the Simeas P Power Meter are shown on Picture 2.


Picture 2: SIMEAS P Power Meter Inputs/Outputs



SIMEAS P Power Meter Features

> Measurement of voltage, current, active & reactive power, frequency, active & reactive energy, power factor, symmetry factor, voltage and current harmonics up to the 21st, total harmonic distortion;
> Single-phase, three-phase balanced or unbalanced connection, four-wire connection;
> PROFIBUS-DP orMODBUS RTU/ASCII or IEC 60870-5-103 communication protocol;
> Simple parameterization via front key or RS485 communication port using SIMEAS P PAR software;
> Graphic display with background illumination with up to 20 programmable screens;
> Battery: Recordings like limit value violations or energy counter values stay safely in the memory up to 3 months in case of a blackout;
> Real-time clock;
> 1 MB memory management: The allocation of the non-volatile measurement memory is programmable;
> Selectable screen types 2, 3, 4 or 6 measured values in one screen;
> One list screen for minimum, average and maximum values;
> Two types of screens for harmonics;
> One screen for oscilloscope function (sampled values or r.m.s. values);
> One screen serving as phasor (vector) diagram;
> Up to 20 screen types can be programmed. Switching from one screen to another can be automatic or manual.


Source: Siemens Energy.

3 comments:

  1. Your blog awesome, you shared valuable information about in #Power quality in electrical system. We provide more information in Harmonic distortions is one of the most common and irritating problems in industrial environment. We need to identify the source of harmonics and suppress them for a quality supply of power. Please visit Harmonic Analysis

    ReplyDelete
  2. This comment has been removed by the author.

    ReplyDelete